Skip to content

Case study / Commercial office building

Critical overheating at an incoming connection inside the chiller control cabinet, running nearly 140°F above ambient on a 480V system.

Critical
FacilityCommercial office building
ScaleMulti-floor occupied building
EngagementAnnual infrared inspection
Max temp219.9°F
Delta T139.6°F

The situation

Inspection of electrical distribution equipment supplying building systems in an occupied commercial office building, including the chiller control cabinet serving building cooling.

The finding

Critical overheating at an incoming connection inside the chiller control cabinet, running nearly 140°F above ambient on a 480V system.

The outcome

Flagged as critical. Backup cooling equipment was available. Corrective action was scheduled before the connection could fail or cause further equipment damage.

Related industry: Commercial Buildings

Want Infinite Infrared to inspect your facility?

See how an electrical infrared inspection can help identify developing problems before they become outages or safety concerns.

Ready to find the problems before they find you?

See a real sample report, or request an inspection for your facility.