A conductor not fully seated in a breaker lug inside a rectifier circuit — identified through visual inspection after a small thermal rise prompted a closer look.

Potential
FacilityTelecommunications facility
ScaleCritical infrastructure site
EngagementAnnual infrared inspection
Max temp91.6°F
Delta T10.7°F

The situation

Inspection of DC power plant equipment and rectifier circuits at a telecommunications facility running on redundant backup systems.

The finding

A conductor not fully seated in a breaker lug inside a rectifier circuit — identified through visual inspection after a small thermal rise prompted a closer look.

The outcome

Repaired on-site during the inspection visit. The redundant system had been masking the thermal signature, demonstrating why opened visual inspection — not just thermal imaging — is part of the service.