Critical overheating at a chiller control cabinet connection

Critical overheating at an incoming connection inside the chiller control cabinet of an occupied commercial office building, with a temperature rise of nearly 140°F over ambient.

CriticalHover or tap the image to compare the visual photo
EquipmentChiller control cabinet
IndustryCommercial Office
Problem typeLoose incoming connection
Possible causeLoose Connection(s)
Maximum temperature219.9°F
Temperature rise139.6°F
Voltage480V
Ambient80.3°F

What was found

Thermal imaging identified critical overheating on one of the incoming chiller cabinet connections. The building remained occupied and backup equipment was available.

Why it mattered

This connection fed the chiller control cabinet supplying cooling for an occupied commercial office building.

Potential consequences

Failure could interrupt building cooling and significantly impact occupant comfort and building operation.

Recommendation

Inspect, disassemble, clean and reassemble to proper component torque.