Poor contact in a rooftop RTU disconnect

Abnormal heating inside a non-fused rooftop disconnect supplying cooling equipment, consistent with poor contact at the knife blade or pivot.

PotentialHover or tap the image to compare the visual photo
EquipmentRooftop unit (RTU) disconnect
IndustrySmall Data Center
Problem typePoor contact
Possible causePoor Contact at Knife Blade and/or Pivot
Maximum temperature106.5°F
Temperature rise39.8°F
Voltage120/208V
Ambient66.7°F
LoadNon-fused disconnect

What was found

Thermal imaging identified abnormal heating within the rooftop disconnect supplying cooling equipment serving the data center.

Why it mattered

This disconnect supplied cooling equipment serving the data center.

Potential consequences

Loss of rooftop cooling equipment can increase server temperatures and reduce cooling redundancy.

Recommendation

Inspect, disassemble, clean and reassemble to proper component torque. Replace component if necessary.